EasyManua.ls Logo

Omron E5ZN - Parameter Initialize; Alarm Latch Cancel

Omron E5ZN
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86
Commands and Responses Section 5-9
5-9-18 Parameter Initialize
Command
This command returns all settings to the default values.
This command can be used for setting area 0. If it is used in setting area 1, an
operation error will be returned.
Before executing the command, use an operation command to enable com-
munications writing.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
5-9-19 Alarm Latch Cancel
Command
This command cancels the alarm latch. The command can be used in setting
area 0 or 1. The corresponding alarm output latch status will be cancelled
when latch cancel is specified.
Note This command is supported by upgraded pulse output models and analog output mod-
els only.
MRC
“30” 05”
SRC
Command
code
Related
information
“0B”
“00” or “10”
MRC SRC
Response code
“30” 05” “0000”
Related
information
Contents
ch Operation mode (See note.)
“00” 1 Cancel alarm latch 1 for ch1
“01” Cancel alarm latch 2 for ch1
“02” Cancel alarm latch 3 for ch1
“0F” Cancel all alarm latches for
ch1
“10” 2 Cancel alarm latch 1 for ch2
“11” Cancel alarm latch 2 for ch2
“12” Cancel alarm latch 3 for ch2
“1F” Cancel all alarm latches for
ch2
“F0” 1, 2 Cancel alarm latch 1 for ch1,
ch2
“F1” Cancel alarm latch 2 for ch1,
ch2
“F2” Cancel alarm latch 3 for ch1,
ch2
“FF” Cancel all alarm latches for
ch1, ch2
MRC
“30” 05”
SRC
Command
code
Related
information
“0C”

Table of Contents