80
Commands and Responses Section 5-9
5-9-7 Communications Writing
Command
This command enables/disables communications writing.
It rewrites the setting for “communications writing.
If communications writing is disabled, operation commands for parameter
rewriting, RUN/STOP, and other operations will be rejected.
Default is communications writing enabled.
This command can be used for setting area 0 or 1.
Response
Response code: The code shown above repres5nts normal completion. For
details on the response code, refer to
5-7 Operation Commands.
5-9-8 Control Start (RUN)/Control Stop (STOP)
Command
This command starts and stops control (RUN/STOP).
This command can be used in either setting area 0 or 1.
Note These variations of the command are supported by upgraded pulse output models and
analog output models only.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
Related
information
Description
”00” or “10” Communications writing prohibited
”01” or “11” Communications writing not pro-
hibited
MRC
“30” “05”
SRC
C
ommand
code
Related
information
MRC SRC
Response code
“30” 05” “0000”
Related
information
Contents
ch Control
“00” 1 RUN
“01” STOP
”10” 2 RUN
“11” STOP
“F0” 1, 2 RUN (See note.)
“F1” STOP (See note.)
MRC
“30” “05”
SRC
Command
code
Related
information
“01”
MRC SRC
Response code
“30” 05” “0000”