Specifications Appendix A
Characteristics
Note 1. The indication of K thermocouples in the 200 to 1,300°C range, T and N thermocouples at a temperature of
100°C or less, and U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication of B
thermocouples at a temperature of 400°C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
2. Ambient temperature: 10°C to 23°C to 55°C
Voltage range: 15 to +10% of rated voltage
3. When 0 to 20 mA DC is selected, the accuracy for 0 to 4 mA is ±0.5% FS + 0.7 mA.
When 0 to 5 VDC is selected, the accuracy for 0 to 1 V is ±0.5% FS + 0.175 V.
Ratings/Specifications for Setting Display Unit (Sold Separately)
Indication accuracy Thermocouple:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Platinum resistance thermometer:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Analog input: ±0.5% FS ±1 digit max.
CT input: ±0.5% FS ±1 digit max.
Temperature
variation influence
(See note 2.)
Thermocouple (R, S, B):
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouples:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at 100°C max: ±10°C max.
Platinum resistance thermometer:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
Voltage variation
influence
(See note 2.)
Transfer output Accuracy: ±0.5% FS (See note 3.)
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band
(P)
0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3,999 s (in units of 1 second)
Derivative time (D) 0 to 3,999 s (in units of 1 second)
Control period 1 to 99 s (in units of 1 second)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1999 to 9999 (decimal point position dependent on input type)
Sampling period 500 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 600 VAC 50 or 60 Hz 1min
Vibration resistance
10 to 55 Hz, 10 m/s
2
for 2 hrs. each in X, Y and Z directions
Shock resistance
150 m/s
2
max. 3 times each in 3 axes, 6 directions
Protective structure Temperature Controller Module IP00
Terminal Unit IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Weight Temperature Controller Module Approx. 90 g
Basic Terminal Unit Approx. 100 g
Expansion Terminal Unit Approx. 80 g
Supply voltage 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 1 W
Indication method 7-segment digital display and single-light indicator
Ambient temperature 10 to 55°C (with no condensation or icing)
Ambient humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)