182
Specifications Appendix A
Characteristics
Note 1. The indication of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of
−100°C or less, and U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication of B
thermocouples at a temperature of 400°C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
2. Ambient temperature: −10°C to 23°C to 55°C
Voltage range: −15 to +10% of rated voltage
3. When 0 to 20 mA DC is selected, the accuracy for 0 to 4 mA is ±0.5% FS + 0.7 mA.
When 0 to 5 VDC is selected, the accuracy for 0 to 1 V is ±0.5% FS + 0.175 V.
Ratings/Specifications for Setting Display Unit (Sold Separately)
Indication accuracy Thermocouple:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Platinum resistance thermometer:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Analog input: ±0.5% FS ±1 digit max.
CT input: ±0.5% FS ±1 digit max.
Temperature
variation influence
(See note 2.)
Thermocouple (R, S, B):
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouples:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at −100°C max: ±10°C max.
Platinum resistance thermometer:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
Voltage variation
influence
(See note 2.)
Transfer output Accuracy: ±0.5% FS (See note 3.)
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band
(P)
0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3,999 s (in units of 1 second)
Derivative time (D) 0 to 3,999 s (in units of 1 second)
Control period 1 to 99 s (in units of 1 second)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range −1999 to 9999 (decimal point position dependent on input type)
Sampling period 500 ms
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 600 VAC 50 or 60 Hz 1min
Vibration resistance
10 to 55 Hz, 10 m/s
2
for 2 hrs. each in X, Y and Z directions
Shock resistance
150 m/s
2
max. 3 times each in 3 axes, 6 directions
Protective structure Temperature Controller Module IP00
Terminal Unit IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Weight Temperature Controller Module Approx. 90 g
Basic Terminal Unit Approx. 100 g
Expansion Terminal Unit Approx. 80 g
Supply voltage 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 1 W
Indication method 7-segment digital display and single-light indicator
Ambient temperature −10 to 55°C (with no condensation or icing)
Ambient humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)