14
Using the I/O Section Section 2-2
2-2-3 Wiring
The left sides of the terminal numbers in the following diagram are on the out-
side of the Unit and the right sides are on the inside of the Unit.
Power Supply Connect to terminals 19 and 20, as shown in the following diagram.
When reinforced insulation is required, connect the I/O to a device without
an exposed charged section or to a device with basic insulation suitable
for the maximum usage voltage of the I/O section.
UL/CSA/CE Safety Standards
Use a SELV power supply with an overcurrent protection function.
A SELV power supply refers to a power supply with redundant I/O or with
increased insulation and with an output voltage of 30 Vr.m.s and a 42.4-V
peak or maximum 60 VDC.
Recommended power supply: S82K-05024 CD (OMRON) or S8VS-
06024A (OMRON)
To ensure the rating of Main terminal disturbance voltage for class A in
EN61326, equip a noise filter (DENSEI-LAMBDA, MXB-1206-33 or equiv-
alent one) to the DC power line as close to the temperature controller as
possible.
Inputs Connect channel 1 to terminals 10 to 12 and channel 2 to terminals 4 to 6 as
follows, according to the input type:
Note Connect the terminals or set the parameter according to the following instructions to
prevent error indicators being lit for channels not being used.
For upgraded pulse output models and analog output models:
With any type of sensor, the parameter “sensor error indicator used” (initial setting level) can
be used to prevent error indicators being lit for channels not being used.
For the previous pulse output models (not upgraded):
For thermocouple, infrared temperature sensor, or analog input:
Form a short-circuit between terminals 5 and 6 when channel 2 is not used, or between
terminals 11 and 12 when channel 1 is not used.
•For Pt:
Connect a resistance of 100 to 125
between terminals 4 and 5 when channel 2 is not
used, or between terminals 10 and 11 when channel 1 is not used.
Form a short-circuit between terminals 5 and 6 when channel 2 is not used and between
terminals 11 and 12 when channel 1 is not used.
19
21
20
13
14
15
7
8
9
1
2
3
22
23
24
16
17
18
10
11
12
4
5
6
E5ZN-SCT24S-500
19
20
+
24-DC input
power supply
19
21
20
13
14
15
7
8
9
1
2
3
22
23
24
16
17
18
10
11
12
4
5
6
E5ZN-SCT24S-500
13
14
15
7
8
9
1
2
3
16
17
18
10
11
12
4
5
6
E5ZN-SCT18S-500
+
10
11
12
+
4
5
6
V
+
4
5
6
V
+
ch1
10
11
12
4
5
6
10
11
12
ch1ch1 ch2ch2ch2
Thermocouple or infrared
temperature sensor
Pt
Analog input