27
Setting Output Specifications Section 3-4
Note When “Cooling control output for ch 1” has been set for an output, ch 1 performs heat-
ing/cooling control. When “Cooling control output for ch 2” has been allocated to the
output, ch 2 performs heating/cooling control.
• With analog output models (E5ZN-2C@F03@-FLK), if alarm output is allo-
cated to OUT1 (control output 1), OUT2 (control output 2), SUB3 (auxil-
iary output 3), or SUB4 (auxiliary output 4), or if the control method is set
to ON/OFF control, the ON output will be 100% output and the OFF out-
put will be 0% output.
Allocating Alarm 2
Output for ch 1 to SUB2
Auxiliary Output 2
Use host communications or the E5ZN-SDL Setting Display Unit to set 3 as
the auxiliary output 2 allocation.
Allocating PV Transfer
Output for ch 2 to SUB3
Auxiliary Output 3
Use host communications or the E5ZN-SDL Setting Display Unit to set 17 as
the auxiliary output 3 allocation.
Name Set value Function
Analog output models
E5ZN-2C@F03@-FLK
Pulse output models
E5ZN-2Q@H03@-FLK
E5ZN-2T@H03@-FLK
SUB3 (auxiliary
output 3)
Terminals 16 and
17
0 ch1 Heating control output
1 Cooling control output (See note.)
2 Alarm 1 and sensor error alarm
OR output
3 Alarm 2 output
4 Alarm 3 output
5 ch2 Heating control output
6 Cooling control output (See note.)
7 Alarm 1 and sensor error alarm
OR output
8 Alarm 2 output
9 Alarm 3 output
10 ch1 SP transfer output
11 Ramp SP transfer output
12 PV transfer output
13 Heating MV transfer output
14 Cooling MV transfer output
15 ch2 SP transfer output
16 Ramp SP transfer output
17 PV transfer output
18 Heating MV transfer output
19 Cooling MV transfer output
SUB4 (auxiliary
output 4)
Terminals 16 and
18
0 to 19 Same as above.
17 ch2 PV transfer output