62
Using Transfer Output Section 4-12
Temperature Controller Settings:
Sensor input type (initial setting level):
2 (platinum-resistance thermometer, 0.0
°C to 100.0 °C)
Control output allocation 2 (initial setting level):
17 (PV transfer output for ch2)
OUT2 transfer output upper limit (initial setting level):
100.0 (
°C)
OUT2 transfer output lower limit (initial setting level):
0 (
°C)
Current output type (initial setting level):
0 (4 to 20 mA DC)
Meter Setting Example:
Inputs for 4 to 20 mA DC are scaled to 0.0 to 100.0
°C.
Input type (initial setting level: in-t): 4 to 20 mA DC (4-20)
Scaling input value 1 (initial setting level: inp.1): 4 mA (4.00)
Scaling display value 1 (initial setting level: dsp.1):0 (00000)
Scaling input value 2 (initial setting level: inp.2): 20 mA (20.00)
Scaling display value 2 (initial setting level: dsp.2):100 (01000)
Decimal point (initial setting level: dp): One decimal place (0000.0)
UNIT
BPS
POWER
ERROR
SD/RD
OUT1
OUT2
SUB1
SUB2
E5ZN
OUT2
(analog current output)
Terminals 1 and 2
Analog Input (E5)
Analog Input (E6)
−
+
Thermocouple
Transfer output
4 to 20 mA DC
Process Meter
K3MA-J AC/DC24V
MAX/MIN LEVEL MODE SHIFT UP
Temperature Controller
E5ZN-2C@F03@-FLK
Channel 2 input
(Thermocouple input)
Terminals 4, 5, and 6
B (White/black)
A (Red)
B (Black/white)
E52-P20A D=3.2 @M