MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
101
25.4 Re-enable zone (H2/B4)
Disabled zones are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
When all zones have been re-enabled, The LED "Disablements" (L8)
will be turned OFF, if there are no other disablements in the system.
NOTE! It is not possible to collectively re-enable a number of alarm
points (zone-address) that are individually disabled via menu H2/B2.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B4.
Re-enable zone
ACCEPT? B4
"A"
Re-enable zone: 000
ACCEPT? L
If there are no zones to re-
enable, menu B4 will be
shown again.
L=a list in which you can
scroll.
If it's the correct zone to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone and
press "A" to accept.
"A"
Re-enable zone
ACCEPT? B4
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.