MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
163
36 Replacing a TLON connection
board and/or a main board
By the TLON network programming, some unique data will be stored
on the 1590 TLON connection board and some unique data will be
stored on the 1556 Main board.
After replacing a TLON connection board to another or replacing both
a TLON connection board and a main board, do "Replace", "Update"
and "Save" in TLON Manager. (In TLON Manager version 2.0,
"Save" will be automatically done after "Update".)
After replacing a main board to another (not the TLON connection
board), do "Update" and "Save" in TLON Manager. (In TLON
Manager version 2.0, "Save" will be automatically done after
"Update".)