Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
97
25.1 Disable zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are
disabled except the addressable manual call points.
Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
"A"
Disable zone: 000
ACCEPT?
Write zone number (e.g.
001)
Disable zone: 001
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
(Default is current time + 3 hours)
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
"A"
Disable zone: 000
ACCEPT?
If more disablements shall
be done, continue like
above. If not, press
"Return" to menu B1.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.