Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
135
28.10 Activate address setting mode for DU
(H5/A9)
This function can be used by commissioning / service engineer to
activate the address setting mode in the following Display Units
connected to an Ext. FBP / DU interface board 1587 in the c.i.e.:
Ext. Presentation unit 1728
Alert Annunciation unit 1735 / 1736
Ext. FBP 1826 / 1828
A specific unit or all units connected to one 1587 board can be
activated for address setting.
NOTE! The units have to be in operation and in quiescent condition,
i.e. the units have to have an address already.
Activate address setting mode for DU
CU 00, 1587-board 0, DU 00 ACCEPT?
Write control unit number,
the board number (0-1)
and the unit's address (99 =
All units on the selected
1587-board). Press "A" to
accept.