MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
107
25.9 Disable / Re-enable alarm devices (H2/B9)
Outputs
95
programmed as type 3 = alarm device (sounder) can be
disabled all at the same time. Disabled alarm devices means that
even if the control expression (trigger condition) for output
respectively is fulfilled, the output will not be activated.
Disabled alarm devices are indicated by LED Fault / Disablements
"Alarm devices" (L13) and LED "Disablements" (L8) and is also
shown in menu H4/U1.
The outputs in one or more control units can be disabled or the outputs
in all control units.
The outputs will be disabled until re-enabled again (via this menu).
NOTE! This function is not the same as push button "Silence alarm
devices" (P3), see chapter ""Silence Alarm devices"", page 28. This
function has higher priority than "Silence alarm devices".
Press "1" or "0", write the
CU number (or "99" for all
CUs)
97
and press "A" to
accept.