31.5 Acknowledge SERVICE signal (H8/S4)
See chapter "Sensors activating SERVICE signal (H4/U6)", page 122.
When service signal from a sensor is acknowledged, the sensor is
given a default sensor value (for a new / clean sensor), i.e. first
replace the sensor, then acknowledge the service signal as soon as
possible.
The first week average sensor value (after acknowledge) will be
calculated within one hour and thereafter each week.
NOTE! If a sensor is replaced without having generated service
signal, it has to be reset to the default sensor value, see chapter "Clear
weekly average (H8/S5)", page 146.
According to chapter
"Access code for
maintenance", see page
141.
Acknowledge SERVICE signal
ACCEPT? S4
Sensor : xxxxxx needs service
L
NOTE! The list order in this menu is as follows:
a) Technical number order in the control unit this menu is
opened.
b) Technical number order in the rest of the system.
If there are no sensors to
acknowledge, menu S4
will be shown again.
L = a list in which you can
scroll. If it is the correct
sensor to acknowledge,
press "Fault acknowledge".
If not, scroll or write the
wanted sensor and press
"Fault acknowledge" or
press "Return" to S4.
The service signal for that sensor is now acknowledged and
the next sensor will be shown in the display.
Sensor : yyyyyy needs service
L
If more service signal
acknowledgements shall
be done, continue like
above. If not, press
"Return" to menu S4.
Acknowledge SERVICE signal
ACCEPT? S4
Scroll or press "Return" to
menu H8. Scroll or press
"Return" to log off.
LED "Service" (L12) will be turned off when all sensors have been
acknowledged.