MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
142
31.2 Disable or re-enable outputs for routing
equipment (H8/S1)
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled via this menu. They stay disabled, until re-enabled again via
this menu. Can be useful during an installation test period, when only
local alarms are required.
Disabled outputs are indicated by LEDs "Disablements" (L8) and
"Fault / Disablements Fire brigade tx" (L15).
Disabled outputs are listed in menu H4/U1.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page
141.
Disable or re-enable outputs for
routing equipment ACCEPT? S1
"A"
Routing equipment for FIRE:1, FAULT:1
(1=enabled, 0=disabled) ACCEPT?
To move the cursor, press
"". Edit and/or press "A"
to accept.
"A"
Disable or re-enable outputs for
routing equipment ACCEPT? S1
Scroll or press "Return" to
return to H8. Scroll or
press "Return" to log off.