Panasonic EBL512 - Change access code for daily duties (H10)

Panasonic EBL512
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
158
32.4 Disable interlocking output (H9/C4)
Interlocking outputs (Type = Interlocking) can be disabled via this
menu but not via menu H2/B3.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. If "000/00" is entered, all interlocking outputs will
be disabled at the same time.
Up to 200 interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
The LED "Disablements" (L8) is also indicating one or more disabled
interlocking outputs.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H9.
Interlocking outputs and inputs
ACCEPT? H9
"A"
Activated interlocking outputs/inputs
ACCEPT? C1
Scroll to menu C4.
Disable interlocking output
ACCEPT? C4
"A"
Disable interlocking output
area 000 point 00 ACCEPT?
Write the area and point,
e.g.:
Disable interlocking output
area 001 point 01 ACCEPT?
Press "A" to accept and/or
"Return" to menu C3.
"A"
Disable interlocking output
ACCEPT? C4
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.