MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
128
28.3 Sensitive fault detection mode (H5/A2)
To increase the possibilities to detect faults during the commissioning,
it is possible to use the "Sensitive fault detection mode. (The time
delay for each fault will be reduced).
NOTE! Don't forget to turn off this mode after the commissioning.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
(H5)", see page 126.
Scroll to menu A2
Sensitive fault detection mode
ACCEPT? A2
"A"
Sensitive fault detection mode: 0
(0 = off, 1 = on)
Press "A" or "1" and "A"
to accept. ON is indicated
by LED "Fault tx
activated" (L11) and the
"Fault" output for routing
equipment. This mode is
ON until turned OFF in
this menu (A2).
"A"
or
"1", "A"
Sensitive fault detection mode
ACCEPT? A2
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.