MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
149
31.9 Safe shut down of control unit (H8/S8)
It's not recommended to power off a control unit (i.e. no 230 V AC
and no battery) without first doing a safe shut down of control unit.
118
Safe shut down will save the SSW and put the CPU at rest. See also
chapter "Restart", page 88.
It's recommended to do a safe shut down after commissioning the
installation and after the calibration of supervised outputs, change of
access code etc. in order to save the new values, codes etc.
Safe shut down can be performed from any control unit and any
control unit can be selected, e.g. a control unit without a front has to
be shut down from another control unit.
NOTE! By restart and power off, the Fault tx output(s) will be
"activated".
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page
141.
Scroll to menu S8.
Safe shut down of control unit
ACCEPT? S8
"A"
Shut down control unit 00 ? 0
(1 = Yes, 0 = No) ACCEPT?
Write the C.U. number,
"1" (=yes) and
"A"
Please Wait ...
Shown for 3 sec. then one
of the three alternatives:
In the CU that will be shut down (when a front is available):
Ready for shut-down, break the power.
Automatic restart within nnn seconds!
Count down starts from
nnn = 300 seconds.
Disconnect the power
supply (mains and battery).
When the power supply is
connected again or after
300 seconds (if powered
all time), there will be an
automatic reset / restart.
In the CU:s that will not be shut down:
Control unit xx ready for power off
No reply from the selected CU xx, i.e. no safe shut down:
No reply from control unit.
FAULT: Restart CU xx code xx yyyyyyy
Date: mm-dd Time: hh:mm Serviced
NOTE! The date is in the Ukrainian convention (S/W
version > 2.2.3) and the Australian convention shown
as DD-MM.
After restart / power on
(see page 88), there will be
a fault activated. This fault
has to be acknowledged,
see chapter "Acknowledge
FAULTS (H6)", page 138.
118
If not, a fault ("FAULT: Read/write site data (SSW), CU xx") might be
generated when you power up the control unit again.