MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
126
28.1 Access code for service (H5)
Access code to level 4 is required.
If login to level 2 was made with code for level 4, no code is required
here.
Action
Text in display
Comments
"Access"
According to chapter
"Access", page 92
Perform monthly test
ACCEPT? H1
Scroll to menu H5
Service
ACCEPT? H5
"A"
Access code: _
If login was made with
code for level 4, no
code is needed.
Enter code for level 4
(4 digits)
Access code: ****
The digits are replaced
(****) in the display
NO ACCESS!
The access code was
not correct. Try again.
Calibration of supervised outputs
ACCEPT? A1
The access code was
correct. This is menu
H5/A1. Press "A" to
accept, scroll or press
return to menu H5.