16.7 Acknowledged alarm
NOTE! Valid for the New Zealand convention only.
A fire alarm presented in the LCD can be acknowledged by pressing
the button "Acknowledge fault" (P6).
Acknowledged alarms are indicated in the fire alarm list in the LCD
by "ACK" in front of the alarm, see page 44. This indication is the
only difference between a fire alarm and an acknowledged alarm.
Acknowledged alarms ("ACK") have to be reset like normal fire
alarms ("ALM").
16.8 Isolated alarm
NOTE! Valid for the New Zealand convention only.
A fire alarm ("ALM") or an acknowledged alarm ("ACK") presented
in the LCD can be isolated as follows:
When the "New Zealand FB Silence switch" (outside switch) is turned
OFF (from activated to not activated), any fire alarm and
acknowledged alarm will be isolated (=disabled).
62
Isolated alarms are indicated in the fire alarm list in the LCD by "ISO"
in front of the alarm respectively, see page 44.
Isolated alarms do not activate any control outputs, do not activate the
output for routing equipment (Fire brigade tx), do not activate the
c.i.e. buzzer and do not activate the LED:s "Fire" in the c.i.e.
Isolated alarms ("ISO") have to be reset like normal fire alarms
("ALM").
Isolated alarms have to be re-enabled via menu H2/B5 before they can
activate a new fire alarm again.
62
LED "Disablements" (L8) is indicating that one or more zones / alarm
points are isolated (disabled).