MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
124
27.8 Configuration (H4/U8)
In a control unit the menu H4/U8 can be used to see the following
settings (made in Win512, "Tools" menu) for that specific control
unit:
Number of addresses that can be used, i.e. xxx = 128, 256 or 512 (set
in "EBL512 settings" dialog box).
Language The language for texts presented in the alphanumeric
display / print-outs. Language file (nnnn.SST) to be downloaded is
selected (in "Download software…" dialog box)
Convention Different countries have different conventions, i.e.
country specific functions, etc. The convention is set (changed) via
Win512, menu Tools | Settings…("Win512 Settings" dialog box).
103
It is not possible to get a print-out from this menu.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H4.
Present system status on display and
printer ACCEPT? H4
"A"
Disablement
Printout: (1=yes) U1
Scroll to menu U8.
Show configuration
U8
Press "A" to accept.
"A"
Max number of allowed loop units xxx
Language:nnnnnnnnnn Conv.:cccccccccc
Press "Return" to menu
U8.
"Return"
Show configuration
U8
Scroll or press "Return"
to menu H4. Scroll or
press "Return" to log off.
103
To set (change) the convention in Win512, Level 2 has to be selected and
a password is required.