MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
82
(disabled) and no alarms or faults can be activated. Disconnected
COM loop is indicated by the LED "Disablements" (L8).
19.2 Single Control Unit
Start the downloading from Win512. A text message will be shown in
the alphanumeric display in the control unit:
Download in progress......
Block nnnn out of xxxx
When the download is completed the following text message will be
shown:
Download completed successfully.
Control unit will now restart
Now, an automatic reset/restart will take place (see chapter "Restart",
page 88.
If the download was not okay the following text message will be
shown:
Checksum fault in downloaded data.
Control unit will now restart
Now, an automatic reset/restart will take place (see chapter "Restart",
page 88.
After the reset/restart another text message will be shown in the
display:
FAULT: Site specific data (SSD), CU nn
Date: MM-DD Time: HH:MM
This text message means that the SSD have not been downloaded, i.e.
a new download has to be performed.
19.3 Control Units in a TLON network
The SSD for all control units can be downloaded via one control unit.
Start the download from Win512. The download will now be
performed to the control units, one at a time, according to the chapter
"Single Control Unit" above.