Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
159
32.5 Re-enable interlocking output (H9/C5)
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
Interlocking outputs (Type = Interlocking) can be re-enabled via this
menu but not via menu H2/B6.
If "000/00" is entered, all interlocking outputs, disabled via menu
H9/C4 and "000/00", will be re-enabled at the same time.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H9.
Interlocking outputs and inputs
ACCEPT? H9
"A"
Activated interlocking outputs/inputs
ACCEPT? C1
Scroll to menu C5.
Re-enable interlocking output
ACCEPT? C5
"A"
Re-enable interlocking output
area 000 point 00 ACCEPT?
This is a list in which you
can scroll. If there are no
disabled outputs, menu C5
will be shown again.
Press "A" (for re-enable)
or "Return" (not re-enable)
to menu C5.
"A"
or
"Return"
Re-enable interlocking output
ACCEPT? C5
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.