31.4 Re-connect loop (H8/S3)
Disconnected (disabled) loops / zone lines (via menu H8/S2) are
indicated by LED "Disablements" and listed in menu H4/U1.
NOTE! When you re-connect a COM loop all the statistics shown in
menu H5/A7 will be erased and set to "0".
According to chapter
"Access code for
maintenance", see page
141.
Re-connect loop
ACCEPT? S3
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit) ACCEPT?
Press:
"0"=COM loop
"1"=BS4 loop
"2"=Expansion board 1580
"3"=Addr. zone interface
2226 / 2335
3361 (MIO).
Press "A" to accept.
"A"
Depending on the
chosen type, 0, 1, 2 or
3, the following will be
shown:
Re-connect COM-Loop: 0, CU: 00
ACCEPT?
Write the required
numbers. Press "A" to
accept.
Re-connect BS4-Loop: 0, Board: 0, CU: 00
ACCEPT?
Re-connect DET8-input: 0, Board: 0,
CU: 00 ACCEPT?
Re-connect input technical no.: 000000
ACCEPT?
Re-connect type: 0 (0=COM, 1=BS4,
2=DET8, 3=Loop Unit) ACCEPT?
Continue to re-connect or
press "Return" to menu S2.
LED "Disablements" will
be turned off if there are
no other disablements in
the system.
Re-connect loop
ACCEPT? S3
Scroll or press "Return" to
return to menu H8. Scroll
or press "Return" to log
off.