MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
46
ZONE: 123 LAST: 789 No.: 003
Re-enable zone: ZZZ ACCEPT?
This is a list of disabled zones. Scroll to or write the wanted zone
number and press "A". If more zones are to be re-enabled, repeat the
procedure.
15.2.2.6 Disable / Re-enable control (X6)
ZONE: 123 LAST: 789 No.: 003
Disable/Re-enable control ACCEPT? X6
Press "A". E.g.:
ZONE: 123 LAST: 789 No.: 003
Dis(=0) or re-en(=1) control? 1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable all control, exting.
and ventilation outputs (H2/B8), page 106.
15.2.2.7 Disable / Re-enable alarm devices (X7)
ZONE: 123 LAST: 789 No.: 003
Disable/Re-enable alarm dev. ACCEPT? X7
Press "A". E.g.:
ZONE: 123 LAST: 789 No.: 003
Dis(=0) or re-en(=1) alarm dev?1 ACCEPT?
To disable, press "0" and "A". (To re-enable, press "1" and "A".). For
more information, see chapter "Disable / Re-enable alarm devices
(H2/B9), page 107.
15.2.3 Alert Annunciation (AA alarm)
When the AA function is enabled, indicated by the LED "Fire brigade
tx delay" (L16), the indications, print-outs, actions etc. are as for a
normal fire alarm except the c.i.e. output for routing equipment
(fire brigade tx) will not be activated. The AA alarm has to be
acknowledged within an acknowledge time and reset within an
investigation time, otherwise the output(s) for routing equipment (fire
brigade tx) will be activated. See EBL512 Planning Instructions for
more information regarding the AA function. Acknowledgement
52
and reset of the AA alarm can be done on a Display unit 2235
53
, an
AA unit 1735 / 1736 or an AA controller 1740. See also chapter
"Alarm reset", page 51.
52
In the "Polish" (CNBOP) and "Czech" conventions, the push button
"Evacuate" (P5) can be used for "AA Acknowledge".
53
LED "Acknowledge" on 2235 is indicating that the push button
"Acknowledge" has been activated. A busy system can cause a time delay
(up to 10 seconds) before the fire alarm is acknowledged.