Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
75
via Win512.
FAULT: Wrong type exp. board x, CU xx
Valid for the 8 zones exp. board 4580, the 8 relay outputs exp. board
4581 and the Inputs and outputs exp. board 4583, mounted in control
unit no. xx.
Check the type of board, which should be the same as programmed
via Win512 version 2.7.x.
FAULT: Wrong type of unit tech no xxxxxx
The unit is not the same type as programmed. Change the
programming or the unit.
FAULT: Zone line input, tech no xxxxxx
Detector mounted in an ADB 2330: faulty / removed detector
or
Ext. line (input) to an ADB 2330: break on a wire or wrong / no end-
of-line resistor
or
Zone interface 2335 / 2226 (input): break on a wire or wrong / no end
of line resistor.
or
Zone interface 2226: No ext. power supply.
or
Multi purpose I/O unit 3361, monitored zone line (input Z): break on
a wire or wrong / no end-of-line capacitor / short circuit (if not
programmed for fire alarm at short circuit).
(User programmable text; External fault)
Programmable input is used for an external fault; see fault message.