MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
95
NOTE_1! During the test, the following information will be shown in
all other c.i.e. displays:
Zones in test mode: 001, 002, 003, 004
NOTE_2! If an alarm point (e.g. a manual call point) is in alarm state
when the test mode is ended, there will not be a fire alarm activated.
Instead the alarm point will be disabled and has to be re-enabled again
via menu H2/B5.
When the "Fire door closing" function is used, the fire door will be
closed when the detectors controlling the door are tested via the test
mode.