4-28 Operating the Drive 590 Series DC Digital Drive
Useful Commands using EI Bisynch ASCII - REM. SEQUENCE
Tag 536, Mnemonic "ow", for example:
/Remote Trip Alarm Ack Jog Mode Jog Start Enable Command
Start Drive 1 0 X 0 1 1 ow>0203
Stop Drive 1 0 X 0 0 1 ow>0201
Disable Drive 1 0 X X X 0 ow>0200
Jog Setpoint 1 1 0 0 1 0 1 ow>0205
Jog Setpoint 2 1 0 1 1 0 1 ow>020D
Remote Trip 0 0 X X X X ow>0000
Reset Alarm a) 1 1 0 0 0 0 ow>0300
Healthy Output Bit 11 goes high
Reset Alarm b) 1 0 X 0 0 0 ow>0200
Sequence Status
SEQ STATUS : Tag 537, Mnemonic "ox" (Read Only)
Reserved bits are undefined when read.
Bit Number Mask Name Comment
0 (lsb) 0x0001 Coast Stop Coast Stop demanded
1 0x0002 Program Stop Program (Fast) Stop demanded
2 0x0004 Disable /Enable demanded
3 0x0008 Run Drive Start demanded
4 0x0010 Jog Drive Jog demanded
5 0x0020 Reserved Undefined
6 0x0040 Alarm Unacknowledged alarm, (Health Store != 0)
7 0x0080 Reserved Undefined
8 0x0100 Running Contactor in and drive ready to be enabled
9 0x0200 Enabled Drive is enabled.
10 0x0400 Zero Speed Zero speed Output TAG 17
11 0x0800 Healthy Output Healthy Output TAG 12
12 0x1000 Ready Ready Output TAG 559
13 0x2000 Reserved Undefined
14 0x4000 Reserved Undefined
15 (msb) 0x8000 Reserved Undefined