6-18 The MAN - MACHINE INTERFACE (MMI) 590 Series DC Digital Drive
CONFIGURE DRIVE
The CONFIGURE DRIVE menu contains many of the important parameters used during set-up when using the MMI.
NOTE The FUNCTION BLOCKS\MISCELLANEOUS\CONFIGURE DRIVE menu contains a different set of parameters, for set-up
using the configuration tool.
Refer to Chapter 4: "Operating the Drive" - Setting-up the Drive to see the most important parameters being used.
CONFIGURE DRIVE (MMI view)
Parameter Tag Range
SETUP PARAMETERS
Function Blocks
FLD. CTRL MODE 209 See below
Selects between open-loop VOLTAGE CONTROL or closed-loop CURRENT
CONTROL.
Refer to FIELD CONTROL
FLD. VOLTS RATIO 210 0.0 to 100.0 % (h)
Sets the output dc field voltage as a ratio of the RMS FIELD supply voltage when FLD
CTRL MODE is set to VOLTAGE CONTROL.
Refer to FIELD CONTROL
MAIN CURR. LIMIT 421 0.00 to 200.00 %
Independent symmetric current clamp. Sets symmetric clamps outside scaling from the
CUR. LIMIT/SCALER parameter.
Refer to CURRENT LOOP
AUTOTUNE 18 OFF/ON
Turns the AUTOTUNE procedure on. Refer to Chapter 4: "Operating the Drive" -
Performance Adjustment.
Refer to AUTOTUNE