590 Series DC Digital Drive Programming
D-13
5703 OUT
This function block is used to define the value that is sent via the P3 port when the selected protocol is
“5703 MASTER” or “5703 SLAVE”.
• In 5703 MASTER mode, the INPUT value is transmitted with a minimum period of 5ms. This period
may be increased using the DELAY parameter. Note that the delay is the time from the start of one
transmission to the start of the next transmission. If the selected baud rate is low then the time to transmit the data may be greater than the delay
time, in which case the delay parameter has no effect.
• In 5703 SLAVE mode, the INPUT value is transmitted every time a value is received. The DELAY parameter is ignored in this mode.
5703 OUT
Parameter Tag Range
INPUT 714 -300.00 to 300.00 %
The value that will be sent via the P3 port when the P3 MODE is either “5703 MASTER” or “5703 SLAVE”.
DELAY 897 0 to 1000 ms
A delay parameter that may be used when in 5703 MASTER mode to increase the time between successive transmissions of the 5703 setpoint value.