B-6 Certification 590 Series DC Digital Drive
PDS of Category C3
PDS of rated voltage less than 1000V, intended for use in the second environment and not intended for use in the first environment
PDS of Category C4
PDS of rated voltage equal to or above 1000V, or rated current equal to or above 400A, or intended for use in complex systems in the second
environment
The drive is generally a category C3 apparatus. Some of the equipments with higher ratings might be classified in Category C4; but for certification,
and as an aid to builders of complex system, the emission limits and immunity levels associated with category C3 have been applied.
Parker SSD Drives' certification (DoC) is supported by tests undertaken in accordance with harmonised standard BS EN61800-3
United States of America & Canada
Compliance
The US have many municipalities that have laws, codes or regulations which require a product to be tested by a nationally recognized testing
laboratory before it can be sold in their area. Parker SSD Drives adopt the nationally recognised Underwriters Laboratories (UL) mark to demonstrate
compliance.
Products are also certified for the Canadian market obtained through UL and their memorandum of understanding with the Canadian Standards
Agency (CSA).
Parker SSD Drives obtain product certification to UL508C “Power Conversion Equipment” for the US market, and C22.2 No.14 “Industrial
Control Equipment” for the Canadian market.
Conditions for Compliance with UL508c
Solid-State Motor Overload Protection
NOTE An external motor overload protective device must be provided by the installer.
The maximum internal overload protection level (current limit) is 150% for 30 seconds and 200% for 10 seconds.
Motor overload protection is provided by means of the thermal device in the motor winding. This protection cannot be evaluated by UL, hence it is the
responsibility of the installer and/or the local inspector to determine whether the overload protection is in compliance with the National Electrical Code
or Local Code requirements.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker 591C and is the answer not in the manual?

Parker 591C Specifications

General IconGeneral
BrandParker
Model591C
CategoryServo Drives
LanguageEnglish

Related product manuals