EasyManua.ls Logo

Parker 591C - Filtering

Parker 591C
401 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
590 Series DC Digital Drive Installing the Drive
3-7
Filtering
NOTE Refer to Appendix B: "Certification" - EMC.
For compliance in Europe with EN61800-3 Table 11:
The CE marking of drives whose armature current >100A is applicable without filtering.
The CE marking of drives whose armature current <100A is only applicable with filtering. The drive requires one of the following:
1. The specified filter given in Appendix B
(also refer to
External AC Supply EMC Filter Installation, page 3-37)
2. Co
mpliant filtering offered by the System
3. Capacitors fitted between phase and earth (see
Figure 3- 1 below)
Start
Contactor
AC
Line
Choke
Drive
C4
C1,C2 & C3
SuitableBranch
Protection Fuse
or
Circuit Breaker
PE
(must be
fitted)
590AC Line Choke Filter
CO468398
Capacitor Reference Number Capacitor Value/Type
C1, C2, C3
3.0μF 400V, EMI suppressor type Class X1
C4
1.0μF 400V, EMI suppressor type Class X1
Figure 3- 1 AC Line Choke and Capacitors fitted to Frame 1 (15A & 35A) & Frame 2 (40A & 70A) Drives

Table of Contents