590 Series DC Digital Drive Programming
D-25
ANALOG OUTPUTS
This function block converts the demand percentage into
0-10V, suitable for driving the analog output electronics of the drive.
ANALOG OUTPUTS
Parameter Tag Range
INPUT 678, 679 -300.00 to 300.00 %
Analog output value as a percentage of range.
% TO GET 10V 245, 248 -300.00 to 300.00 %
Scaler value which produces 10V output. Set % to get 10V to 50% to get ±10V out for ±50% in.
OFFSET 464, 465 -100.00 to 100.00 %
Offset value added to the normal output value after the scaler and before the modulus.
MODULUS 362, 363 FALSE / TRUE
Unipolar analog output enable. If TRUE, then -10% gives +1V out.
ANOUT 1 (A7) to ANOUT 2 (A8) 55, 56
.xx V (h)
Actual voltage output to the terminal.
INPUT
OFFSET
MODULUS
DIAGNOSTIC
X
X

Table of Contents