4-4 Operating the Drive 590 Series DC Digital Drive
Setting-up the Drive
IMPORTANT
You must not exceed the maximum drive and motor ratings. Refer to the Product Code or maximum rating label, and the
motor rating plate.
NOTE Refer to Chapter 6: “The Man-Machine Interface (MMI)” to familiarise yourself with the MMI’s LED indications, and how to use the keys
and menu structure.
The following instructions are written in logical order. Complete each stage successfully before progressing to the next.
Calibration
NO POWER IS CONNECTED AT THIS STAGE
You must first calibrate the Converter for use with the motor:
The settings for Armature Current, Field Current, Armature Voltage and the Tacho Calibration Option Board (if fitted) are selected on the control
board. Lift the hinged terminal cover to reveal the switchable calibration panel and the switchable tacho calibration option board (if fitted).
TACHO CALIBRATION
OPTION BOARD
SWITCHABLE CALIBRATION PANEL
TEST
POINTS