590 Series DC Digital Drive Programming
D-39
DEADBAND
When the input is within the deadband, the output is clamped to zero to ignore any noise. The limits are
symmetrical around zero. The limits are set by the DEADBAND parameter.
Deadband width
DEADBAND
Parameter Tag Range
INPUT 1 100 -200.00 to 200.00 %
Input 1 value. By default this is connected to Analog Input 1 (terminal A2).
DEADBAND 131 0.0 to 100.0 %
Range within which the output is clamped at zero.
OUTPUT 700
.xx %
Modified value of input.