590 Series DC Digital Drive Programming
D-99
SEQUENCING
This function block contains all the parameters relating to the sequencing (start and stop) of
the drive.
SEQUENCING
Parameter Tag Range
AUX START 161 OFF / ON
Software Start/Run command. Auxiliary Start is ANDed with the Start input, C3, to generate Drive Start. This should normally be left ON.
AUX JOG 227 OFF / ON
Software Jog command. Auxiliary Jog is ANDed with the Jog input, Tag 496 (by default C4), to generate Drive Jog. This should normally be left
ON.
AUX ENABLE 168 OFF / ON
Software Enable command. Auxiliary Enable is ANDed with the Enable input, Tag 497 (by default C5), to generate Drive Enable. This should
normally be left ON.