590 Series DC Digital Drive Programming
D-49
DIGITAL INPUTS
Use this block to control the digital
operating parameters of the software.
DIGITAL INPUTS
Parameter Tag Range
VALUE FOR TRUE 103, 106, 109, 1239, 1242 -300.00 to 300.00 %
The output value when input is TRUE, that is:
Digital Input 1, terminal C6 = 24V (True)
Digital Input 2, terminal C7 = 24V (True)
Digital Input 3, terminal C8 = 24V (True)
VALUE FOR FALSE 104, 107, 110, 1240, 1243 -300.00 to 300.00 %
The output value when input is FALSE, that is:
Digital Input 1, terminal C6 = 0V (False)
Digital Input 2, terminal C7 = 0V (False)
Digital Input 3, terminal C8 = 0V (False)
OUTPUT 680, 681, 682, 1238, 1241
.xx %
The output value, this is either VALUE FOR TRUE or VALUE FOR FALSE.
DIGIN 1 (C6) to DIGITAL INPUT C5 71, 72, 73, 69, 70 OFF / ON
The Boolean representation of the actual voltage applied to the terminal.
The digital input can be
configured to link to a destination
location, and to set that
destination TRUE or FALSE
depending upon programmable
values.