590 Series DC Digital Drive Parameter Specification Tables
C-7
Tag Mn Function Block Name Parameter Name Minimum Maximum Default Units Range Notes
95 cn AUX I/O AUX DIGOUT 2 0 1 0 0: OFF
1: ON
V0 W0
96 co AUX I/O AUX DIGOUT 3 0 1 0 0: OFF
1: ON
V0 W0
97 cp LINK 13 SOURCE TAG -1298 1298 77 V0 W2
98 cq LINK 14 SOURCE TAG -1298 1298 122 V0 W2
99 cr LINK 15 SOURCE TAG -1298 1298 125 V0 W2
100 cs DEADBAND INPUT 1 -200.00 200.00 0.00 % V1 W0
102 cu LINK 20 DESTINATION TAG 0 1298 90 V0 W2
103 cv DIGITAL INPUT 1 VALUE FOR TRUE -300.00 300.00 0.01 % V0 W0
104 cw DIGITAL INPUT 1 VALUE FOR FALSE -300.00 300.00 0.00 % V0 W0
105 cx LINK 21 DESTINATION TAG 0 1298 118 V0 W2
106 cy DIGITAL INPUT 2 VALUE FOR TRUE -300.00 300.00 0.01 % V0 W0
107 cz DIGITAL INPUT 2 VALUE FOR FALSE -300.00 300.00 0.00 % V0 W0
108 d0 LINK 22 DESTINATION TAG 0 1298 119 V0 W2
109 d1 DIGITAL INPUT 3 VALUE FOR TRUE -300.00 300.00 0.01 % V0 W0
110 d2 DIGITAL INPUT 3 VALUE FOR FALSE -300.00 300.00 0.00 % V0 W0
111 d3 ALARMS 5703 RCV ERROR 0 1 0 0: ENABLED
1: INHIBITED
V0 W0
112 d4 ALARMS STALL TRIP 0 1 0 0: OK
1: FAILED
V1 W4
113 d5 RAMPS RAMPING 0 1 0 V1 W4
114 d6 SEQUENCING SEQ STATE 0 15 0 0: SEQ INIT
1: SEQ INIT
2: SEQ HOLD
3: SEQ STANDBY
4: SEQ PRE READY
5: SEQ READY
6: SEQ AUTOTUNING
7: SEQ RUN
8: SEQ AT ZERO SPD.
9: SEQ QUENCH
10: SEQ PROGRAM
STOP
11: SEQ STOP
12: SEQ DELAY STOP
13: SEQ COAST STOP
14: SEQ ERROR
15: CURRENT DECAY
V0 W4
115 d7 ALARMS HEALTH WORD 0x0000 0xFFFF 0x0000 V1 W4