590 Series DC Digital Drive Programming
D-101
SEQUENCING
Parameter Tag Range
SYSTEM RESET 374 FALSE / TRUE
Set for one cycle as the drive is enabled.
READY 125 FALSE / TRUE
The drive is ready to accept an enable signal.
SEQ STATE 114 See below
0: SEQ INIT
1: SEQ INIT
2: SEQ HOLD
3: SEQ STANDBY
4: SEQ PRE READY
5: SEQ READY
6: SEQ AUTOTUNING
7: SEQ RUN
8: SEQ AT ZERO SPD.
9: SEQ QUENCH
10: SEQ PROGRAM STOP
11: SEQ STOP
12: SEQ DELAY STOP
13: CURRENT DECAY
14: SEQ COAST STOP
15: SEQ ERROR
START (C3) 68 OFF / ON
State of the Start/Run terminal.
PROGRAM STOP 80 FALSE / TRUE
State of program stop (Terminal B8). When B8 is at 24V, then PROGRAM STOP is FALSE.
COAST STOP 525 FALSE / TRUE
State of coast stop (Terminal B9). When B9 is at 24V, then COAST STOP is FALSE.
OPERATING MODE 1295 TERMINALS / COMMUNICATIONS
Output parameter that indicates the current sequencing control source.