3-16 Installing the Drive 590 Series DC Digital Drive
Power Connections continued
Motor Armature
A+
A-
Connect the
motor
armature to
terminals A+
and A-.
The motor armature is connected to busbar terminals
A+ and A-. If a DC contactor is used the poles should
be interposed between the controller terminals and the
motor terminals.
Note:
When the controller is operating in a
regenerating mode for extended periods
acting as a load generator for another
machine, it is advisable to fit additional
protection in the armature circuit. A DC
fuse or a high speed circuit breaker will
provide this protection, if in doubt consult
the Parker SSD Drives Engineering
Department.
Motor Field
D3
D4
Connect the
motor field (-)
to terminal D3
and connect
field (+) to
terminal D4.
Connect the motor field (-) to terminal D3 and field
(+) to terminal D4. If the motor has no field
connections, is a permanent magnet motor, or if the
field is derived externally, you must inhibit the
FIELD ENABLE parameter.
MMI Menu Ma
p
1
SETUP PARAMETERS
2
FIELD CONTROL
FIELD ENABLE
PE
star
+
F+ F-
point
D3
D4
+
PE
M
A+ A
-
PE
star
point