Technical details
Operating Manual PNOZ s30
1001715-EN-19
| 105
Relay outputs 750330 751330
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
External contact fuse protection,
auxiliary contacts
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24 V AC/DC,
characteristic B/C 4 A 4 A
Conventional thermal current 4 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Times 750330 751330
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 50 ms 50 ms
With automatic start after power
on typ. 3.920 ms 3.920 ms
With automatic start after power
on max. 4 s 4 s
With manual start typ. 40 ms 40 ms
With manual start max. 100 ms 100 ms
Delay-on de-energisation
With power failure typ. UB 240 V 100 ms 100 ms
With power failure max. UB 240
V 150 ms 150 ms
With power failure typ. UB 24 V 25 ms 25 ms
With power failure max. UB 24 V 50 ms 50 ms
After safety function is triggered
typ. 8 ms 8 ms
After safety function is triggered
max. 15 ms 15 ms
Recovery time at max. switching
frequency 1/s
After power failure 4 s 4 s
After safety function is triggered 1 s 1 s
Reaction time after limit value is
exceeded 1/f_ist + 16 ms 1/f_ist + 16 ms