Operation and diagnostics
Operating Manual PNOZ s30
1001715-EN-19
| 93
List of errors
Error no. Error message Description Remedy
2 PNOZ s30 cold started The unit is ready for op-
eration
(Error stack entry)
For information only
3 Brown Out occurred Supply voltage too low Check supply voltage
4 Softwarerestart The PNOZ s30 has
been restarted via a
software restart. This
can be caused by one
of the following reas-
ons:
} Restart via the Re-
start menu
} Restart via the
PNOZsigma Config-
urator
} Restart using the
special function "Error
acknowledgement"
} Restart using the
special function "Re-
start"
For information only
5 SIM loaded Device parameters
have been transferred
from the chip card
For information only
2000 Wrong signal A ... /Z Implausible signal from
the encoder
Ensure that there is no open circuit in
the wiring of input A ... /Z
} Ensure that the correct encoder is
configured and connected
} Ensure that the encoder operates cor-
rectly
2001 AB frequency > fmax AB The maximum fre-
quency of the encoder
at tracks AB was ex-
ceeded
} Enter a max. frequency for "Track AB
fmax" that is not exceeded during nor-
mal operation
} Ensure that a suitable encoder is con-
nected
2004 Z frequency > fmax Z The maximum fre-
quency of the encoder
at track Z was ex-
ceeded
} Enter a max. frequency for "Track AB
fmax" that is not exceeded during nor-
mal operation
} Ensure that a suitable encoder is con-
nected