16 Technical data
Main features
Type(s): Specification(s)
Consumption: Maximum 12 watts, without metering accessories connected.
Power supply requirements: 90 ... 240VAC 50/60Hz
Electrical protection: Fuses 160 mA. Resetting by power interruption
Operating temperature (°C): -5 °C ... 45 °C (23 °F ... 113 °F)
Material: ABS or polycarbonate (USA and Canada)
Dimensions of the housing: Length: 280 mm Width: 219 mm Height: 156 mm
Weight of the bag: 0.850 kg
Display: 5-inch LCD colour screen, resistive touch
Environment:
Storage temperature: -10 °C ... 70 °C (10 °F ... 158 °F)
Air humidity: Max. 90% non-condensing
Degree of protection: IP 65
Product certification: CE
Electromagnetic compatibility: Class B break tests conform to EN61326-1.
Class B break tests conform to the standard EN61326-2-6.
Class B break tests conform to EN55011.
Harmonic tests conform to EN61000-3-2.
Harmonic tests conform to EN61000-3-3.
The interference immunity tests conform to EN61000-4-2.
Interference immunity tests conform to EN61000-4-3.
Interference immunity test EN61000-4-4.
The interference immunity tests conform to EN61000-4-5.
The interference immunity tests conform to EN61000-4-6.
Interference immunity tests conform to EN61000-4-8.
The interference immunity tests conform to EN61000-4-11.
Standard: EN 61000 Electromagnetic compatibility (EMC)
EN 61326 Electrical equipment for measuring, control and labora‐
tory use for a standard environment (class B for residential use)
Inputs:
Potentiometric inputs: 2 inputs
4-20 mA inputs: 2 insulated inputs
2 non-insulated inputs
Digital inputs: 4 inputs
USB inputs: USB connector on the front of the box
Outputs:
Relay outputs: 2 self-fed relay outputs
Relay outputs: 2 ON/OFF relay outputs
Technical data