PLX51-PBM Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway User Manual
ProSoft Technology, Inc. Page 62 of 196
The PROFIBUS configuration consists of the following parameters:
Table 3.17 Field Device PROFIBUS configuration parameters
Parameter
Description
Node Address
This is the station address configured for the added device. This is
the address the DP PROFIBUS Master will use to look for and
configure the device for Data Exchange.
TSDR
N/A
Minimum Slave Interval
N/A
Watchdog Enable
N/A
Watchdog Value
N/A
Group Membership
N/A
Byte/Word Swap Option
This parameter will reformat the input and output Profibus DPV0
communication data. Below are the reformat options if the normal
data format is AA BB CC DD:
None
BB AA
DD CC BB AA
CC DD AA BB