EasyManua.ls Logo

ProSoft Technology PLX51-PBM - Multi-Connection

ProSoft Technology PLX51-PBM
196 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLX51-PBM Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway User Manual
ProSoft Technology, Inc. Page 82 of 196
3.10.3 Multi-Connection
The PLX51-PBM supports up to four Class 1 (cyclic data exchange) connections.
This will allow the user to have more field devices per PLX51-PBM because more
data can be exchanged between the Logix controller and the PLX51-PBM.
IMPORTANT: This only applies when the user has implemented the PLX51-PBM into Logix using an
EDS AOP. When using a Generic Module Profile in Logix (pre-Logix v21) the user will only be able to
use 1 Logix Connection.
When the user verifies the PLX50 Configuration Utility project (this is done by right-
clicking on the device and selecting Verify Configuration), the software will indicate if
all the current configuration will fit into the selected EtherNet/IP Connection count. If
not, the user will need to increase the connection count.
In the PLX50 Configuration Utility the user can set the number of EtherNet/IP
Connections in the Logix tab of the configuration window (as shown below):
Figure 3.109 PLX50CU EtherNet/IP Connection Count
In Logix the user can increase/decrease the connection count using the EDS AOP
(as shown below):
Figure 3.110 Logix EtherNet/IP Connection Count

Table of Contents

Related product manuals