Rockwell Automation Publication 5094-UM001C-EN-P - April 2019 89
Configure the Standard Module Chapter 6
Discover Modules
To use the Discover Modules method with FLEX 5000 I/O modules, complete
these steps.
1. Go online with your Logix Designer application.
The project must include a FLEX 5000 EtherNet/IP adapter.
2. Right-click the FLEX 5000 EtherNet/IP adapter and choose Discover
Modules.
The Logix Designer application automatically detects available modules
that are connected to the backplane.
3. At the Select Module Type window, click Create to add the discovered
module to your project.