7-14 Setting the Relay Date Code 20010731
SEL-352-1, -2 Instruction Manual
Table 7.6: SET P (Port) Command Settings
Setting
Name
Description Setting Range
Port Settings (See Section 8: Serial Port Communications and Commands)
PROTO Setting for selecting ASCII or addressed protocol SEL, LMD, DNP (DNP for
SEL-352-2 Relay only)
PREFIX Prefix character for addressed LMD protocol #, $, %, &, @
ADDRESS Number for LMD protocol address 1–99
SETTLE Serial Port settling time 0–30 sec
SPEED Serial Port Communication baud rate (300, 1200, 2400, 4800,
9600, 19200, 38400)
D_BITS Serial Port Communication Data Bits 7, 8
PARITY Serial Port Communication Parity Bit, none,
even, or odd
N, E, O
STOP Serial Port Communication Stop Bits 1, 2
TIMEOUT Serial Port timeout 0–30 min
1-min steps
AUTO Automatic Messages enabled on this port Y, N
RTS_CTS Hardware flow control enabled on this port (not
available on EIA-485 Port 1)
Y, N
FAST_OP Fast Operate Enable Y, N
For DNP settings, see Appendix G: Distributed Network Protocol (DNP) 3.00
Table 7.7: SET T Command Settings
Setting Name
Description Setting Range
NLB1–NLB16 Name of the local bit 14 characters
SLB1–SLB16 Text label to display when the local bit is set 7 characters
CLB1–CLB16 Text label to display when the local bit is clear 7 characters
PLB1–PLB16 Text label to display when the local bit is pulsed 7 characters
DP1_0–DP16_0 Text label to display when DPn Relay Word bit is 0 16 characters
DP1_1–DP16_1 Text label to display when DPn Relay Word bit is 1 16 characters
DEFAULT SETTINGS
The following settings are the factory default settings for a nominal 5 A relay. For a nominal
1 A relay, divide the following settings by 5: 50FT, 50LD, 50N, 37OP, 26CP, 26CF, 26TP,
26TF, 50MD. If an R_S command is issued, the default settings will be the new active settings.