Date Code 20010731 Setting the Relay 7-15
SEL-352-1, -2 Instruction Manual
Relay versions with only 1 or no I/O boards come from the factory with CLSLOG = OFF so
settings CLSdo through CLSC do not appear. However, the R_S command will restore the
following settings in all versions of the relay.
=>SHO<ENTER>
Group 1
RELID =EXAMPLE SEL-352-1
TRMID =EXAMPLE CIRCUIT BREAKER
Topen = 33 Tclose = 66 SlowTr = 42.0 SlowCl = 83.0
CTR = 600 XPTR = 4300 YPTR = 4300
SALOG = OFF
50FT = 8.60 FTLOG = 2
FCpu = 4.000
50LD = 0.50 50N = 0.50 LDLOG = 1
LPpu = 3.25 LDpu = 5.50
37OP = 2.07 47Q = 18.7 87TH = 4.3
VNpu = 10.00 Kmag = 5.0 Kang = 10.0 THLOG = ON
OPpu = 3.00
26CP = 1.110 26CF = 1.450 26TP = 3.490 26TF = 4.560
CRTC = 80 TRTC = 80
87H = 57.0 87FO = 4.0 59H = 100.0 FOLOG = 1
FPpu = 25.00 FFpu = 30.00
46UB = 16 UBLOG = ON
UCpu = 6.00 UPpu = 50.00 UFpu = 60.00
DELOG = OFF
59L = 57.0 27D = 10.0 CLSLOG = 1 CLSdo = 5.00
RCApu = 0.00 RCBpu = 0.00 RCCpu = 0.00
RTPLOG = 1
SBLOG = OFF
M86T =FBF + LBF + TTF + CTF + FOBF + UBBF
50MD = 0.10 TRLOG = 2
M2pu = 600.000 M3pu = 600.000
MER =UBPF + LPF + FOPF + LODPF + TRIPA + TRIPB + TRIPC +
CLOSE + MCLOSE + 26CPA + 26CPB + 26CPC + 26TPA + 26TPB +
26TPC + MDT
OUT101 =86BFT
OUT102 =86BFT
OUT103 =BALRM
OUT104 =!50MNA*!50MNB*!50MNC*!52AA*!52AB*!52AC
OUT105 =MDT
OUT106 =LPF + FOPF + UBPF
OUT107 =86RS
DP1 =IN104
DP2 =0
DP3 =0
DP4 =0
DP5 =0
DP6 =0
(continued on next page)