1-6 Introduction and Specifications Date Code 20080110
SEL-387E Instruction Manual
Cyclic Capacity (2.5 cycles/second):
24 V 0.75 A L/R = 40 ms
48 V 0.50 A L/R = 40 ms
125 V 0.30 A L/R = 40 ms
250 V 0.20 A L/R = 40 ms
High Current Interrupting Option:
Make: 30A; Carry: 6 A continuous carry at 70°C, 4 A continuous carry at 85°C;
1 s rating: 50 A; MOV protected: 330 Vdc, 130 J;
Pickup time: Less than 5 ms; Dropout time: Less than 8 ms, typical
Breaking Capacity (10000 operations):
24 V 10 A L/R = 40 ms
48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms
250 V 10 A L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for thermal dissipation):
24 V 10 A L/R = 40 ms
48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms
250 V 10 A L/R = 20 ms
Note: Do not use high current interrupting output contacts to switch ac control signals. These outputs
are polarity dependent.
Note: Make per IEEE C37.90-1989; Breaking and Cyclic Capacity per IEC 60255-23
[IEC 255-23]: 1994.
Optoisolated Inputs: 250 Vdc: Pickup 200–300 Vdc; Dropout 150 Vdc
125 Vdc: Pickup 105–150 Vdc; Dropout 75 Vdc
110 Vdc: Pickup 88–132 Vdc; Dropout 66 Vdc
48 Vdc: Pickup 38.4–60 Vdc; Dropout 28.8 Vdc
24 Vdc: Pickup 15.0–30 Vdc
Note: 24, 48, and 125 Vdc optoisolated inputs draw approximately 4 mA of current, 110 Vdc inputs
draw approximately 8 mA of current, and 250 Vdc inputs draw approximately 5 mA of current.
All current ratings are at nominal input voltage.
Routine V, I inputs, optoisolated inputs, output contacts: 2500 Vac for 10 s;
Dielectric Strength: Power supply: 3100 Vdc for 10 s; EIA-485 communications port: 2200 Vdc
Frequency System Frequency: 50 or 60 Hz; Phase Rotation: ABC or ACB;
and Rotation: Frequency Tracking Range: 40.1–65.0 Hz
Note: V
A
required for frequency tracking.
Serial
Communications
Ports: EIA-232: 1 front and 2 rear; EIA-485: 1 rear, 2100 Vdc isolation; Baud rate: 300–19200 bps
Ethernet
Communications
Port:
Application Protocols
FTP to Card: 1 server session (supports IEC 61850 CID files)
Telnet to Card: 1 server session (supports SEL ASCII)
Telnet to Host: 1 server session (supports SEL ASCII, SEL Compressed ASCII,
Fast Meter, and Fast Operate)
IEC 61850: 6 MMS sessions
16 incoming GOOSE messages
8 outgoing GOOSE messages
Protocol Stacks
TCP/IP
OSI

Table of Contents