Date Code 20080110 Introduction and Specifications 1-7
SEL-387E Instruction Manual
Ports (PORT 5 and PORT 6)
PORT 5 is supported.
PORT 6 will be enabled with a future firmware upgrade.
Physical Layer Options (PORT 5 and PORT 6)
10/100BASE-T: 10/100 Mbps, RJ-45 connector
100BASE-FX: 100 Mbps, LC connector
Indicators (PORT 5 and PORT 6)
Link: Green LED is on when the link is operational
Activity: Red LED blinks when there is transmit or receive activity
Time-Code Input: Relay accepts demodulated IRIG-B time-code input at Port 1 or 2. Relay is time synchronized to
within ±5 ms of time source input.
Operating Temp.:
–40° to +85°C (–40° to +185°F)
Weight:
2U rack unit height: 15 lbs (6.8 kg); 3U rack unit height: 17.75 lbs (8 kg)
Type Tests: *Generic Emissions, Heavy Industrial: EN 50081-2:1993, Class A
*Generic Immunity, Heavy Industrial: EN 50082-2:1995
*Radiated and Conducted Emissions: EN 55011:1998, Class A
*Conducted Radio Frequency: EN 61000-4-6:1996,
ENV 50141:1993,
10 Vrms
Radiated Radio Frequency
(900 MHz with modulation): ENV 50204:1995, 10 V/m
Cold: IEC 60068-2-1 [IEC 68-2-1]:1990, EN 60068-2-1:1993,
Test Ad, 16 hours at –40ºC
Dry Heat: IEC 60068-2-2 [IEC 68-2-2]:1974, EN 60068-2-2:1993, Test
Bd, 16 hours at +85ºC
Damp Heat, Cyclic: IEC 60068-2-30 [IEC 68-2-30]:1980, Test Db, 25° to 55ºC,
6 cycles, 95% humidity
Dielectric Strength: IEC 60255-5 [IEC 255-5]:1977 and IEEE C37.90-1989
2500 Vac on analogs, contact inputs, and contact outputs; 3100
Vdc on power supply; 2200 Vdc on EIA-485 communications
port
Impulse: IEC 60255-5 [IEC 255-5]:1977, 0.5 J, 5000 V
Vibration: IEC 60255-21-1 [IEC 255-21-1]:1988, Class 1
Shock and Bump: IEC 60255-21-2 [IEC 255-21-2]:1988, Class 1
Seismic: IEC 60255-21-3 [IEC 255-21-3]:1993, Class 2
1 MHz Burst Disturbance: IEC 60255-22-1 [IEC 255-22-1]:1988, Class 3
Electrostatic Discharge: IEC 60255-22-2 [IEC 255-22-2]:1996,
IEC 61000-4-2 [IEC 1000-4-2]:1995,
Level 4
Radiated Radio Frequency: IEC 60255-22-3 [IEC 255-22-3]:1989,
ENV 50140:1993,
IEEE C37.90.2-1995,
35 V/m, no keying test,
frequency element accurate to 0.1 Hz
Fast Transient Disturbance: IEC 60255-22-4 [IEC 255-22-4]:1992,
IEC 61000-4-4 [IEC 1000-4-4]:1995
Level 4