Date Code 20080110 Communications 7-37
SEL-387E Instruction Manual
The front-panel LEDs remain remapped until the front panel times out, the TAR R command is
executed, or the <TARGET RESET> button is pushed.
Refer to Section 4: Control Logic for a list of the Relay Word bits and their corresponding rows.
TAR R (Reset Targets)
Access Levels 1, B, 2
The TAR R command resets the default row for the TAR and TAR F commands to 0, and
remaps the second row of front-panel LEDs to display Row 1, which is the standard target
display. It also resets any tripping front-panel targets.
Use the TAR R command to return the front-panel LEDs to the standard targets when you are
done using the TAR or TAR F command for testing.
TEST DB
Access Levels B, 2
Use the TEST DB name 01 [name02name10][s] command to pulse up to 10 binaries (Relay
Word bits), where name01name10 are the Device Word bits that are to be pulsed and s is the
number of seconds to pulse the binaries. The range for s is 1 to 30 seconds with a default of one
second. If the binary is a logical 0, the command will pulse it to one. If the binary is a logical 1,
the command will pulse it to zero. This command affects both SER and IEC 61850
communications.
TFE (Through-Fault Event Report)
The TFE command displays the following data for each individually recorded through-fault
event:
Date and time of the through fault
Duration (seconds) of the through fault
Maximum current (Amps primary) for each monitored current input
The following cumulative values (updated for each new through-fault event) are also displayed:
Through-fault count
Simple I
2
t calculation for each monitored current input
There are various choices for the TFE command, listed briefly below. Refer to Section 5:
Metering and Monitoring for a complete description of the through-fault event reports:
TFE Displays cumulative and individual through-fault event data. The twenty (20) most
recent individual events are displayed.
TFE A Displays cumulative and individual through-fault event data. All the most recent
individual events are displayed, up to 1200.
TFE C Clears/resets cumulative and individual through-fault event data.