2 SEL-387E Relay Command Summary Date Code 20080110
SEL-387E Instruction Manual
CEV n Show compressed winding event report number n, at 1/4-cycle resolution.
Attach DIF for compressed differential element report, at 1/4-cycle resolution.
Attach R for compressed raw winding data report, at 1/16-cycle resolution.
Attach Sm for 1/m-cycle resolution. (m = 4 or 8 for filtered data; m = 4, 8, 16, 32, or
64 for raw data)
DAT Show date presently in the relay.
DAT m/d/y Enter date in this manner if Date Format setting DATE_F = MDY.
DAT y/m/d Enter date in this manner if Date Format setting DATE_F = YMD.
EVE n Show standard event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE D n Show digital data event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE DIF1 n Show differential element 1 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE DIF2 n Show differential element 2 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE DIF3 n Show differential element 3 event report number n, with 1/4-cycle resolution.
Attach S8 for 1/8-cycle resolution.
EVE R n Show raw analog data event report number n, with 1/16-cycle resolution.
Attach Sm for 1/m-cycle resolution. (m = 4, 8, 32, 64)
GOOSE Display transmit and receive GOOSE messaging information. Enter number k to
scroll the GOOSE data k times on the screen.
GRO Display active setting group number.
HIS n Show brief summary of the n latest event reports.
HIS C Clear the brief summary and corresponding standard event reports.
INI Reports the number and type of interface boards in the relay.
IRI Force synchronization attempt of internal relay clock to IRIG-B time-code input.
MET k Display metering data, in primary amperes. Enter number k to scroll metering k times
on screen.
MET D k
Display demand metering data, in primary amperes. Enter number k to scroll metering
k times on screen.
MET DIF k Display differential metering data, in multiples of tap. Enter number k to scroll
metering k times on screen.
MET E Display energy metering data.
MET H Generate harmonic spectrum report for all input currents, showing first to 15th
harmonic levels in secondary amperes.
MET P k Display peak demand metering data, in primary amperes. Enter number k to scroll
metering k times on screen.
MET RD n Reset demand metering values. (n = 1, 2, 3, A)
MET RP n Reset peak demand metering values. (n = 1, 2, 3, A)
MET SEC k Display metering data (magnitude and phase angle), in secondary amperes. Enter
number k to scroll metering k times on screen.
SER n Show the latest n rows in the Sequential Events Recorder (SER) event report.

Table of Contents